80W Customized Power Supply

600w-kaiguandianyuan

Input Condtion
Model NO.
Output Rail

Output
current

Voltage Accuracy
Regulation
Efficiency
Max Power
Line
Load
90~264V~
47~63Hz
Input current
 1.5A Max.
KRP-HF87
KRP-HF87-A
+12V
6.66A
±5%
±0.5%
±1%
86%
82%
80W
KRP-HF88
KRP-HF88-A
+15V
5.33A
±5%
±0.5%
±1%
86%
82%
80W
KRP-HF89
KRP-HF89-A
+24V
3.33A
±5%
±0.5%
±1%
86%
85%
80W
KRP-HF8T
KRP-HF8T-A
+48V
 1.67A
±5%
±0.5%
±1%
86%
85%
  80W

80W Customized Power Supply

Features:

  • Design for BF application

  • Meet 2 X MOPP and Contact Leakage < 100uA

  • Safety Class II & EMI Class B

  • Follow ErP Directive of EU

  • High mechanical torque start-up

  • -40℃ to +70℃ operating temperature

  • 5,000m operation altitude

  • Convection cooling for rated load

  • Forced air for max. load

General Specifiations:

  • Input voltage: 90V AC to 264V AC

  • Input frequency: 47Hz to 63Hz

  • Inrush current (cold start at 25℃): <30A at 1150V AC or <60A at 230V AC

  • Hold up time: 16ms

  • Over-voltage protection: latch off

  • Short-circuit protection: auto recovery

  • Over load protection: auto recovery

  • Operating temperature: -40℃ to 70℃ derating: 2.5%/℃>50℃

  • Storage temperature: -40℃ to +85℃

EMI:

  • EN55011 "B"

  • EN61000-3-3

  • Harmonics: EN61000-3-2 class A

EMS:

  • EN61000-4-2, -3, -4, -5,-6,-8,-11

Safety:

  • UL/CSA/IEC60950-1,2nd edition

  • ANSI/AMMI/CSA/IEC60601-1,3nd edition

  • CB report, CE mark, RM report/file

Notes:

1. Size:  2" (50.8mm) x 4"(80.5mm) x 1.12"(24.0mm)

2. Mounting Hole: 44.5 x 95.3 (mm)

3. Connectors:

  • AC input: JST B2P3-VH or Molex 5277-02A or equivalent

  • DC output: JST B4P-VH or Molex 5273-04A or equivalent

  • Output Pin assignment:1-Vo 2-Vo 3-GND 4-GND

4. Packing:

  • Net weight: 160 g approx./ unit

  • Gross weight: 15 kg approx./carton, 80 units/carton

  • Carton size: 382 (L) x 374 (W) x 277 (H)